Allen-Bradley 1762-IF4 does not support engineering configuration. It supports Raw/Proportional or Scaled for PID. When use Raw/Proportional configuration, it is hard to find out what’s its configuration. After contact Allen-Bradley, here are the limits:

For 4-20 mA configuration:

  1. 0 mA = 0 count
  2. 4 mA = 6241 count
  3. 20 mA = 31206 count
  4. 21 mA = 32767

for 0-10 VDC configuration:

  1. 0 V = 0 count
  2. 1o V = 31206 count
  3. 11 V = 32767